P142 - Protection Functions - V42 - SE-En
P142 - Protection Functions - V42 - SE-En
Feeder Protection
30 – 10 – 2011 SCHEDULE
4 setting groups
!
» CB position contacts should be available on the relay (via opto) when CB control function
is enabled.
!
» It may be necessary to match these values with CB manufacturing data to ensure safe
operation of the CB.
! » This function requires an opto input connected to relay CB Healthy internal data
(via PSL Editor).
Opto Label 06 CB Healthy
DDB #037 DDB #230
1 3
» Battery Status
!
» In case of power supply failure, the battery will save
the date, time, events, disturbance & fault recorder.
» Settings/PSL are saved in EEPROM memory : no
battery is required to save data even without power
supply.
» Battery life time is 1 year if relay is not supplied or
10 years if relay is permanently supplied.
» Select via Menu : Active setting group is » Select via Opto : Active setting group is
selected by operator action (relay front panel or selected automatically viaOpto1 and Opto2 (only
front/rear communication to PC). these 2 optos).
» Notes : Opto 1 and 2 can be used for other
applications
Opto 1 0
» Active setting group is selected via the Opto 2
0 Group 1
parameter Active Settings
Opto 1 1
Group 2
Opto 2 0
» Notes : 0
Opto 1
» Opto inputs 1 and 2 must be Group 3
set in the PSL Opto 2 1
!
» It is advised to disable non-used
setting groups
IA
5.62A
P P
i u i u
u u
i i
Q Q
i u u i u u
i i
Mode 2 Mode 3
P P
i u i u
u u
i i
Q Q
i u u i u u
i i
Direction of energy displayed on the relay depends on
the selected mode
100%
80%
1
60%
Previous state*
! 0
» Opto can be damaged if overvoltage
occurs (more than300VDC ) 0%
* Schmitt Trigger
Schneider Electric - Energy Automation – 09/2010 43
Opto Configuration
» PSL :
Phase
selective Start
Any phase
Phase
selective Trip
Any phase
tRESET = 0
I>1
TIMER
TRIP
tRESET ≠ 0
I>1
TIMER
TRIP
Schneider Electric - Energy Automation – 09/2010 51
Overcurrent (50/51/67)
Vrms
I>1
V<
k.I>1
tRESET = 0
I2>1
TIMER
TRIP
tRESET ≠ 0
I2>1
TIMER
TRIP
Schneider Electric - Energy Automation – 09/2010 61
Negative Sequence Overcurrent (46)
» based on IN calculation
» based on Sensitive IN
measurement
tRESET = 0
IN>1
TIMER
TRIP
tRESET ≠ 0
IN>1
TIMER
TRIP
Schneider Electric - Energy Automation – 09/2010 73
Earth Fault Protection (50N/51N/67N)
» SEF/REF Add-ons
Wattmetric
It is possible to add a power criteria from existing
elements by choosing Wattmetric characteristic
» SEF/REF Add-ons
Note : It is possible to use both low impedance REF and DTS/Wattmetric function while
using high impedance REF is exclusive
» Element VN>1
» Timer before threashold
reinitialisation
tRESET = 0
VN>1
TIMER
TRIP
tRESET ≠ 0
VN>1
TIMER
TRIP
Schneider Electric - Energy Automation – 09/2010 84
THERMAL OVERLOAD (49)
Note :
» Single characteristic (one time constant) is
used to protect cables or dry transformers.
» Dual characteristic (two time constants) is
used for oil insulated transformers with natural
air cooling
» one time constant protects against
slow increase of oil temperature
» one time constant protects against fast
increase of windings temperature
Note : It is possible to modify the 4 phase overcurrent elements and the first element of
earth fault 1 & 2 functions.
Note : Elements will appear in Cold Load Pickup function only if they are enabled in the
relevant PHASE OVERCURRENT & EARTH FAULT functions.
» Cold Load Pickup function activation is linked to circuit breaker position. It is thus necessary to
wire CB position on relay digital inputs.
» CB position is managed by two signals: 52A (CB CLOSED) & 52B (CB OPEN). If only one signal
is available, the other one will automatically be calculated by the protection.
52A
52B
Function
activation
tclp tcold
Note : If CB position (52A or 52B) is not available, it is possible to activate the function
using the signal « CLP initiate ». Behaviour will be the same as 52B signal (check above
diagram).
Note : It is possible to modify elements 3 & 4 for OVERCURRENT, EARTH FAULT 1 &
2 and SENSITIVE EARTH FAULT (SEF).
Note : if Selective Logic function is disabled, signals such as I>3 Timer Block will
completely block the corresponding element while if Selective Logic function is enabled,
element is not blocked anymore but new timer settings will be applied.
VAN
50 V VAN 50 V
VAN
VAN
50 V 50 V
»Operating mode:
Note : measurement mode and operating mode are defined for each function UNDER
VOLTAGE & OVERVOLTAGE. They will be applied for all elements of each function.
» Function definition
» Function definition
Setting definition:
» Threashold value
» Timer
Note : 4 elements available for UNDER FREQUENCY function and 2 elements for
OVER FREQUENCY function.
» Function configuration
Element configuration :
» Threashold value (df/dt rate in Hz/s)
» Timer (for trip)
» Direction:
» Negative for falling frequency conditions operation
» Positive for rising frequency conditions operation
» Both
Note : after protection trips, if CB is not open before the end of set timer, CB fail element
will operate
Trip
CB Open
No Breaker Failure
CB Fail 1 timer
Bfail 1
activation
Trip.
CB Open
Breaker Failure
CB Fail 1 timer
Bfail 1
activation
Note : VTS operates when a residual voltage is detected without negative sequence
current. In case of loss of voltage on the 3 phases, other calculation will take place to
detect VT failure.
» CT Supervision activation
Note : CTS operates when a zero sequence current (calculated) appears when no zero
sequence voltage is measured or calculated.
When CTS function starts, protection functions based on calculated values (such as
Broken Conductor, Earth Fault 2, Negative sequence overcurrent…) are automatically
blocked.
Other functions can be blocked by customising the PSL using signals « CTS Block » -
instantaneous or « CT Fail Alarm » - time delayed:
Note : distance to fault is displayed in the fault report. It can be displayed as a distance,
as an impedance or as % of line length: