york fan coil & terminal range 2008

Comfort without limits

YORK Fan Coil Units from Johnson Controls


the only names you need to know for a Fan Coil and
terminal unit range to suit all applications,
that has no limits, ranging from the most simple
commercial space up to penthouse office and
apartments. And whatever the challenge Johnson
Controls has the experience to provide units that will
meet your needs.

york fan coil & terminal range 2008

A more comfortable,
safe and sustainable world

fan coils & terminal range 2008

SAPHIR
Fan Coil Unit
2 & 4 pipe system

A complete range from 0.8 kW up to 3.5 kW

19

190

Noise Level

Deep

dB(A)

mm

Welcome to SAPHIR, a new range of aesthetically designed


units, compact and sleek in design.where style and
performance combine to bring you a range of units small in
size, low on noise but high in desirability!

Selection software

Features
Casing available in full range of RAL colours
Casing available with metallic finish
Hot water or electric heating
Vertical and horizontal installation options
Suction and delivery plenum option
Factory fitted valve and controller packages

SAPHIR Fan Coil Unit


0.8 kW to 3.5 kW
Technical features
Model
max
Total cooling capacity [kW]

Sensible cooling capacity [kW]

Water flow in cooling [l/h]

Pressure drop in cooling [kPa]

Heating capacity 2 pipes [kW]

Water flow in heating 2 pipes [l/h] *

Pressure drop in heating 2 pipes [kPa]

Heating capacity 4 pipes [kW]

Water flow in heating 4 pipes [l/h]

Pressure drop in heating 4 pipes [kPa]

(1)

(1)

(1)

(1)

(2)

(2)

(2)

(3)

(3)

(3)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)]

(4)

130

140

230

240

1.50

2.00

2.87

3.52
3.00

med

1.14

1.54

2.39

min

0.83

1.13

1.86

2.29

max

1.16

1.58

2.16

2.70

med

0.86

1.19

1.78

2.27

min

0.62

0.85

1.37

1.70

max

282

342

493

605

med

197

264

410

515

min

143

197

319

394
10.1

max

1.9

2.9

7.0

med

0.9

1.7

5.1

7.6

min

0.5

0.9

3.2

4.7

max

1.98

2.79

3.83

4.82

med

1.49

2.07

3.21

4.05

min

1.09

1.48

2.50

3.07

max

282

342

493

605

med

197

264

410

515

min

143

197

319

394

max

1.6

2.4

5.8

8.4

med

0.7

1.4

4.2

6.3

min

0.4

0.7

2.7

3.9

max

1.94

2.36

3.28

3.73

med

1.59

1.97

2.92

3.38

min

1.25

1.59

2.48

2.84

max

170

206

287

326

med

139

172

256

296

min

109

139

217

248

max

2.2

3.3

10.4

13.2

med

1.5

2.3

8.5

11.0

min

0.9

1.5

6.3

8.0

max

275

390

425

550

med

201

288

330

460

min

125

190

246

325

max

44

53

48

55

med

36

45

43

50

min

28

35

35

41

max

35

44

39

46

med

27

36

34

41

min

19

26

26

32

Power supply [V-ph-Hz]

230 / 1/ 50

Power input [W]

max

31

42

61

63

Absorbed current [W]

max

0.14

0.20

0.29

0.28

Dimensions

Height mm

540

540

540

540

Width mm

900

900

1200

1200

Depth mm

190

190

190

190

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C
(2) Room temperature 20C - Water inlet temperature: 50C
(3) Room temperature 20C - Water inlet temperature: 70/60C
(4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

fan coils & terminal range 2008

LASER
Fan Coil Unit
2 & 4 pipe system

A complete range from 1 kW up to 9.5 kW

Features
LASER fan coil units are simple and elegant, discreet in
their design. High standards of quality and reliability,
combined with a wide range of accessories ensure a
total solution for your comfort cooling and heating
requirements.

Selection software

10 unit sizes, suitable for horizontal or vertical


mounting
Models with or without casing
6 speed fan (3 speeds pre-wired)
Multi-way adjustable discharge grilles
Single coil 2, 3, or 4 rows
double coil 3 or 4 rows (cooling) & 1 row (heating)
Electric heating option
Suction and delivery plenum option
Factory fitted valve (on/off or modulating) and
controller packages
Painted steel feet and back panel option

LASER Fan Coil Unit


1 kW to 9.5 kW
Technical features
Model

Total cooling capacity [kW]

Sensible cooling capacity [kW]

Water flow in cooling [l/h]

Pressure drop in cooling [kPa]

Heating capacity 2 pipes [kW]

Water flow in heating 2 pipes [l/h] *

Pressure drop in heating 2 pipes [kPa]

Heating capacity 4 pipes [kW]

Water flow in heating 4 pipes [l/h]

Pressure drop in heating 4 pipes [kPa]

(1)

(1)

(1)

(1)

(2)

(2)

(2)

(3)

(3)

(3)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)]

(4)

110

112

114

216

218

220

222

224

226

228

max

1.16

1.64

2.41

3.36

3.58

4.53

5.63

6.57

7.41

9.50

med

0.99

1.35

2.1

2.72

3.05

3.75

4.86

5.87

6.81

7.75

min

0.79

1.1

1.75

2.24

2.5

2.99

4.24

4.7

5.61

6.18

max

0.98

1.37

1.96

2.73

3.14

3.62

4.54

5.2

5.86

7.71

med

0.82

1.09

1.68

2.17

2.57

2.91

3.83

4.56

5.32

6.08

min

0.64

0.86

1.36

1.74

2.04

2.25

3.27

3.53

4.26

4.69

max

201

300

394

596

654

802

958

1167

1306

1715

med

173

244

345

487

553

687

863

1074

1224

1286

min

140

197

284

398

452

567

741

842

977

1008

max

3.4

7.1

5.8

11.3

13.6

24.1

28.4

18.8

21

36.9

med

2.8

4.6

9.5

9.8

17.4

21.8

15.5

18.1

25.8

min

3.4

3.3

6.5

6.7

11.6

17.2

10.5

12.8

17.3

max

1.57

2.16

3.05

4.11

4.95

5.71

7.19

7.83

9.33

11.80

med

1.28

1.73

2.43

3.44

4.16

4.65

6.08

6.94

8.51

9.48

min

1.35

2.75

3.35

3.61

5.25

5.45

6.86

7.43

max

100

163

199

307

346

445

499

608

642

839

med

86

134

176

259

294

382

449

562

604

654

min

71

110

147

214

241

318

386

448

489

525

max

2.7

6.1

4.8

11.9

12.5

20

23.5

15.5

20.5

30.4

med

2.3

4.7

3.7

8.5

9.1

14.3

18

12.7

17.6

21.3

min

1.7

3.1

2.8

5.7

6.3

9.5

14.2

8.7

12.4

14.3

max

1.12

1.52

2.25

3.38

3.64

4.92

5.53

6.92

7.18

9.05

med

1.02

1.31

2.06

2.98

3.19

4.16

4.92

6.3

6.8

7.73

min

0.79

1.1

1.68

2.5

2.7

3.38

4.36

5.16

5.71

6.34

max

100

163

199

307

346

445

499

608

642

839

med

86

134

176

259

294

382

449

562

604

654

min

71

110

147

214

241

318

386

448

489

525

max

4.4

8.83

19.3

6.3

13

14.5

34.1

40

53.6
40.7

med

1.6

3.4

15.2

9.7

11.9

28.8

36.4

min

1.07

2.4

6.27

11.4

3.5

6.7

9.6

20.3

26.8

28.6

max

239

328

409

659

780

906

1117

1219

1374

1795

med

192

246

336

495

610

727

956

1086

1253

1210

min

143

185

263

378

459

559

768

786

924

886

max

48

50

54

53

56

54

60

58

63

67

med

42

45

49

48

51

48

56

55

60

60

min

36

38

42

44

43

40

50

47

53

55

max

38

40

42

41

43

41

47

45

50

53

med

33

35

38

36

39

35

42

44

47

45

min

28

29

32

29

32

29

38

37

41

36

Power input [W]

max

46

48

57

81

86

107

156

147

162

211

Absorbed current [W]

max

0.22

0.23

0.27

0.39

0.41

0.48

0.52

0.66

0.68

0.87

Height mm

538

538

538

538

538

614

614

614

614

614

Width

mm

648

773

898

1023

1148

1273

1273

1523

1523

1773

Depth mm

224

224

224

224

224

254

254

254

254

254

Power supply [V-ph-Hz]

Dimensions

230 / 1 / 50 +E

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C
(2) Room temperature 20C - Water inlet temperature: 50C
(3) Room temperature 20C - Water inlet temperature: 70/60C
(4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

fan coils & terminal range 2008

LOW BODY
Fan Coil Unit
2 & 4 pipe system

A complete range from 0.9 kW up to 3.4 kW

430
mm

Height

Features

LOW BODY units are from the LASER family of Fan Coil
Units. Our reduced height cabinet means Low Body
units are the ideal solution for new or replacement
applications where dimensional limitations apply

Selection software

5 unit sizes, suitable for vertical mounting


Models with or without casing
6 speed fan (3 speeds pre-wired)
Single coil 2 or 3 rows
Double coil 2 or 3 rows (cooling) & 1 row (heating)
Electric heating option
Suction and delivery plenum option
Factory fitted valve (on/off or modulating) and
controller packages
Painted steel feet and back panel option

LOW BODY Fan Coil Unit


0.9 kW to 3.4 kW
Technical features
Model

Total cooling capacity [kW]

Sensible cooling capacity [kW]

Water flow in cooling [l/h]

Pressure drop in cooling [kPa]

Heating capacity 2 pipes [kW]

Water flow in heating 2 pipes [l/h] *

Pressure drop in heating 2 pipes [kPa]

Heating capacity 4 pipes [kW]

Water flow in heating 4 pipes [l/h]

Pressure drop in heating 4 pipes [kPa]

(1)

(1)

(1)

(1)

(2)

(2)

(2)

(3)

(3)

(3)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)]

(4)

110

112

114

216

218

max

0.94

1.46

2.11

2.72

3.37

med

0.84

1.22

1.77

2.37

2.95

min

0.69

0.97

1.42

1.95

2.58

max

0.83

1.19

1.69

2.16

2.64

med

0.72

0.97

1.38

1.86

2.29

min

0.57

0.75

1.09

1.5

1.97

max

162

251

364

467

580

med

145

211

305

409

509

min

119

168

246

336

444

max

2.1

12.6

6.9

18.4

med

1.7

2.9

9.3

5.5

14.6

min

1.2

1.9

6.3

3.9

11.5

max

1.26

1.81

2.55

3.27

3.99

med

1.1

1.48

2.09

2.81

3.45

min

0.87

1.14

1.64

2.26

2.97

max

109

157

221

284

2.3

med

96

128

181

244

1.8
1.2

min

76

99

143

196

max

0.8

1.4

4.3

346

6.1

med

0.7

299

4.7

min

0.4

0.6

257

3.6

max

1.15

1.83

2.43

3.27

3.65

med

1.02

1.53

2.03

2.85

3.2

min

0.83

1.22

1.64

2.34

2.8

max

101

161

213

286

320

med

90

134

177

250

280

min

73

107

144

205

245

max

2.2

4.6

10.5

18.9

5.7
4.5

med

1.7

3.3

7.6

14.9

min

1.2

2.2

5.2

10.5

3.6

max

243

321

446

574

691

med

203

246

343

470

570

min

149

178

253

356

470
56

max

50

51

54

54

med

44

46

49

48

51

min

37

39

43

41

44

max

40

41

44

44

46

med

34

36

39

38

41

min

27

29

33

31

34

Power supply [V-ph-Hz]

230 / 1 / 50 + E

Power input [W]

max

46

48

57

81

86

Absorbed current [W]

max

0.22

0.23

0.28

0.39

0.42

Height mm

430

430

430

430

430

Width

mm

648

773

898

1023

1148

Depth mm

254

254

254

254

224

Dimensions

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C
(2) Room temperature 20C - Water inlet temperature: 50C
(3) Room temperature 20C - Water inlet temperature: 70/60C
(4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

10

fan coils & terminal range 2008

YFCM
Fan Coil Unit
with centrifugal fan
2 & 4 pipe system

A complete range from 1.5 kW to 7.5 kW

Selection software

Features
YFCM is a range of Fan Coil Units that continues the YORK
tradition based on high reliability and low noise levels. It
is the result of great commitment in terms of energy and
resources to offer a more modern product from every
point of view: Every detail has been carefully studied to
guarantee for example the symmetric feet, the wide valve
space (170 mm) and easy access to the filter in all models.
Moreover each version has the same internal structure,
identical in both horizontal and vertical models, in order to
standardize production and guarantee a greater flexibility in
distribution and installation.

7 unit sizes, suitable for horizontal or vertical


mounting
Models with or without casing
4 speed fan (3 speeds pre-wired)
Single piece discharge grille
Single coil 3, or 4 rows
Double coil 3 or 4 rows (cooling) & 1 row (heating)
Electric heating option
Suction and delivery plenum option
Factory fitted valve (on/off or modulating) and
controller packages
Painted back panel option

11

YFCM Fan Coil Unit


1.5 kW to 7.5 kW
Technical features
Model

Total cooling capacity [kW]

Sensible cooling capacity [kW]

Water flow in cooling [l/h]

Pressure drop in cooling [kPa]

Heating capacity 2 pipes [kW]

Water flow in heating 2 pipes [l/h] *

Pressure drop in heating 2 pipes [kPa]

Heating capacity 4 pipes [kW]

Water flow in heating 4 pipes [l/h]

Pressure drop in heating 4 pipes [kPa]

(1)

(1)

(1)

(1)

(2)

(2)

(2)

(3)

(3)

(3)

Air flow [m3/h]

Sound power level [dB(A)]

130

140

230

240

330

340

430

440

530

540

630

640

730

740

max

1.50

1.80

2.50

2.80

3.50

3.90

4.00

4.60

4.80

5.70

5.95

6.60

6.31

7.50
6.3

med

1.3

1.5

2.15

2.4

2.9

3.3

3.44

3.9

4.15

4.8

5.08

5.5

5.37

min

1.1

1.3

1.8

2.47

2.7

2.9

3.2

3.6

4.2

4.3

4.6

4.47

5.2

max

1.25

1.48

2.1

2.17

2.95

3.1

3.35

3.8

4.05

4.8

5.5

5.4

6.3

med

1.19

1.68

1.75

2.35

2.49

2.68

3.05

3.24

3.85

4.4

4.3

4.8

min

0.83

0.98

1.39

1.43

1.95

2.05

2.21

2.51

2.67

3.17

3.3

3.64

3.6

4.16

max

260

310

430

485

605

675

690

795

830

985

1030

1140

1160

1295

med

225

260

370

415

500

570

595

675

720

830

880

950

985

1090

min

190

225

310

345

425

465

500

550

620

725

745

795

820

900

max

5.73

13.1

14.1

24.7

11.1

17

17.9

13.6

23.5

23.4

22.7

15

24.4

19.6

med

4.3

9.8

10.6

18

8.3

12.4

13.5

10

18.2

17.6

17.2

11

18.6

14.4

min

3.24

7.9

13.1

8.7

10

7.4

14.2

13.3

13

13.7

10.1

max

2.06

2.3

3.3

3.5

4.45

4.8

5.2

5.8

6.5

7.4

8.8

9.07

10.1

med

1.7

1.95

2.7

3.7

4.35

4.8

5.5

6.2

6.7

7.3

7.5

8.3

min

1.4

1.6

2.3

2.5

3.2

3.65

4.7

5.2

5.5

6.21

6.7

max

155

180

260

270

345

375

405

450

520

570

620

685

710

785

med

130

155

210

235

285

310

335

370

430

485

520

570

590

650
520

min

110

120

180

200

235

250

285

310

365

405

430

470

485

max

3.8

11.4

21.1

11

14.1

14.5

11.1

23.4

21.6

18.4

14.2

25.8

18

med

2.9

5.2

8.6

15.1

8.2

10.3

11

8.2

18.1

14.9

14.1

10.7

19.7

14

min

2.1

3.7

6.5

11.2

7.27

8.2

14.1

12.3

10.4

7.9

14.6

10.4

max

1.75

2.70

3.60

3.69

5.30

5.50

6.10

med

1.35

2.35

3.1

3.31

4.5

5.4

min

1.25

2.05

2.65

2.93

3.9

4.2

4.6

max

150

235

310

315

460

475

530

med

120

205

270

285

390

435

470

min

110

180

230

250

340

365

400

max

3.69

8.6

4.6

3.66

8.8

7.6

9.6

med

2.8

6.7

4.3

2.9

6.9

6.2

7.7

min

2.21

5.25

2.4

2.27

4.7

4.7

5.92

max

300

300

450

450

600

600

750

750

1000

1000

1200

1200

1400

1400

med

240

240

360

360

480

4800

600

600

800

800

950

950

1100

1100

min

190

190

290

290

380

380

480

480

650

650

750

750

950

950

max

51

50

54

54

51

51

54

54

59

58

60

60

66

65

med

45

45

50

50

42

54

48

47

54

50

55

55

62

60

min

40

40

42

43

35

40

45

43

48

44

49

49

55

54

max

42

42

45

45

42

42

45

45

50

49

51

51

57

56

med

36

36

41

41

33

36

39

39

45

41

46

46

53

51

min

31

31

33

34

26

31

36

34

39

35

40

40

46

45

Power input [W]

max

49

50

60

60

95

95

95

95

130

125

180

180

190

190

Absorbed current [W]

max

0.23

0.23

0.28

0.28

0.36

0.36

0.44

0.44

0.74

0.74

0.84

0.84

1.4

1.4

Height mm

530

530

530

530

530

530

530

530

530

530

530

530

530

530

Width

mm

770

770

985

985

1200

1200

1200

1200

1415

1415

1415

1415

1415

1415

Depth mm

225

225

225

225

225

225

225

225

225

225

255

255

255

255

Sound pressure level [dB(A)]

(4)

Power supply [V-ph-Hz]

Dimensions

230 / 1 / 50 + E

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C
(2) Room temperature 20C - Water inlet temperature: 50C
(3) Room temperature 20C - Water inlet temperature: 70/60C
(4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,5 s.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

12

fan coils & terminal range 2008

YFTM
Fan Coil Unit
with tangential fan
2 & 4 pipe system

A complete range from 1.4 kW to 5.3 kW

25
dB(A)

Noise Level

Features

Sister to the YFCM unit range, YFTM units are ideal


for use where reduced noise levels, an increasingly
important issue both for both for designers and end
users, are required. The YFTM series is equipped with a
tangential fan assembly which has a 120 mm diameter,
the largest of its kind on this type of unit, resulting in an
extremely low noise level

Selection software

5 unit sizes, suitable for horizontal/vertical mounting


Models with or without casing
Low noise tangential fan
4 speed fan (3 speeds pre-wired)
Single piece discharge grille
Single coil 3, or 4 rows
Double coil 3 or 4 rows (cooling) & 1 row (heating)
Electric heating option
Suction and delivery plenum option
Factory fitted valve (on/off or modulating) and
controller packages
Painted back panel option

13

YFTM Fan Coil Unit


1.4 kW to 5.3 kW
Technical features
Model

130

140

230

240

330

340

430

440

530

540

1.40

1.70

2.40

2.60

3.40

3.70

4.05

4.50

4.2

5.30

med

1.2

1.45

2.08

2.3

2.8

3.1

3.34

3.75

3.67

4.5

min

1.04

1.2

1.7

1.9

2.3

2.5

2.83

3.15

3.17

max

1.17

1.4

1.7

1.99

2.59

2.62

2.99

3.52

3.45

4.46

med

0.92

1.15

1.36

1.66

2.07

2.08

2.29

2.77

2.79

3.61

min

0.78

0.9

1.1

1.34

1.7

1.69

1.91

2.34

2.28

3.02

max

240

295

415

450

590

640

700

780

795

915

med

210

250

360

400

485

535

580

650

695

780

min

180

210

295

330

400

430

490

545

600

690

max

5.7

14.5

9.2

13.9

20.1

19.7

36.6

20.6

20.6

med

4.6

11.8

7.3

10.5

15

14.8

26.7

16.1

15.6

min

3.4

8.46

5.7

7.7

11.1

11

19.7

12.4

11.9

max

2.08

2.25

3.1

3.3

4.3

4.65

5.02

5.55

6.3

6.9

med

1.66

1.9

2.7

2.8

3.6

3.9

4.2

4.6

5.3

5.8

min

1.45

1.5

2.3

2.4

2.9

3.15

3.5

3.8

4.5

4.8

max

155

170

250

260

335

360

395

430

495

550

med

120

145

200

225

270

295

320

355

410

460

min

110

115

175

190

225

240

270

295

345

385

max

3.68

7.2

9.8

7.6

11

20.8

16.4

33.4

26.1

17.4

max
Total cooling capacity [kW]

Sensible cooling capacity [kW]

Water flow in cooling [l/h]

Pressure drop in cooling [kPa]

Heating capacity 2 pipes [kW]

Water flow in heating 2 pipes [l/h] *

Pressure drop in heating 2 pipes [kPa]

Heating capacity 4 pipes [kW]

(1)

(1)

(1)

(1)

(2)

(2)

(2)

(3)

med

2.9

5.4

8.44

14.8

12.4

24.4

20.5

13.2

min

2.12

3.9

6.2

4.7

6.15

10.8

9.21

17.8

15.6

9.95

max

1.44

2.60

3.50

4.05

4.40

med

1.18

2.25

3.34

3.8

min

1.05

1.95

2.45

2.83

3.28

max

145

225

300

340

380

med

120

195

260

295

330

min

105

170

210

260

280

max

2.4

8.9

3.7

4.36

5.4

med

1.8

6.93

2.9

3.46

4.25

min

1.4

5.43

2.08

2.71

3.28

max

300

300

450

450

600

600

750

750

1000

1000

med

240

240

360

360

480

380

600

600

800

800

min

190

190

290

290

480

380

480

480

650

650

max

48

48

47

48

48

47

54

52

54

56

med

41

40

43

42

43

43

48

46

48

51

min

34

34

36

36

39

36

43

41

44

47

max

39

39

38

39

39

38

45

43

45

47

med

32

31

34

33

34

34

39

37

39

42

min

25

25

27

27

30

27

34

32

35

38

Power input [W]

max

40

40

50

50

65

65

80

80

85

85

Absorbed current [W]

max

0.15

0.15

0.16

0.16

0.2

0.2

0.27

0.27

0.35

0.35

Height mm

530

530

530

530

530

530

530

530

530

530

Width

mm

775

775

990

990

884

884

884

884

1099

1099

Depth mm

225

225

225

225

225

225

225

225

225

225

Water flow in heating 4 pipes [l/h]

Pressure drop in heating 4 pipes [kPa]

(3)

(3)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)]

(4)

Power supply [V-ph-Hz]

Dimensions

230 / 1/ 50 + E

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C
(2) Room temperature 20C - Water inlet temperature: 50C
(3) Room temperature 20C - Water inlet temperature: 70/60C
(4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,5 s.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

14

fan coils & terminal range 2008

YGFC
Fan Coil Unit
2 & 4 pipe system

A complete range from 1.9 kW to 14 kW

Selection software

Features
Our commercial Fan Coil Unit range, The YGFC Series
is designed specially to meet the varied requirements
of zone cooling or heating using Chilled Water or Hot
Water. However in order to meet the growing demand
in city centres where loads are high and space at a
premium, YGFC units have a coil option suitable for use
in district cooling systems, thus helping reduce pumping
power while increasing the overall system efficiency!

10 unit sizes, suitable for horizontal or vertical


mounting
Models with or without casing
3 speed whisper quiet fans
District cooling coil option allows reduction in pump
power and increase in system efficiency
Single coil 3, or 4 rows
Double coil 3 or 4 rows (cooling) & 1 row (heating)
Electric heating option
Suction and delivery plenum option
Range of coil protection options for increased
product longevity

15

YGFC Fan Coil Unit


1.9 kW to 14 kW
Technical features
Model

Total cooling capacity [kW]

Sensible cooling capacity [kW]

Water flow in cooling [l/h]

Pressure drop in cooling [kPa]

Heating capacity 2 pipes [kW]

Water flow in heating 2 pipes [l/h] *

Pressure drop in heating 2 pipes [kPa]

Heating capacity 4 pipes [kW]

Water flow in heating 4 pipes [l/h]

Pressure drop in heating 4 pipes [kPa]

02 ST CB 03 ST CB 04 ST CB 05 ST CB 06 ST CB 07 ST CB 08 ST CB 10 ST CB

(1)

(1)

(1)

(1)

(2)

(2)

(2)

(3)

(3)

(3)

Air flow [m3/h]

Sound power level [dB(A)]

max

2.38

med
min

5.47

12 T CB

14 ST CB

8.78

10.3

13.4

6.74

7.36

8.20

10.1

12.4

6.02

6.18

6.73

7.95

9.93

5.22

5.62

6.56

7.62

9.56

4.92

5.37

6.11

7.42

8.89

4.36

2.30

3.56

4.18

5.10

5.94

1.82

2.79

3.21

4.13

4.87

max

1.73

2.57

3.09

3.87

4.46

med

1.67

2.44

2.95

3.59

4.25

min

1.31

1.89

2.27

2.86

3.37

3.95

4.3

4.87

5.67

6.93

max

410

547

752

839

994

1141

1163

1512

1775

2304

med

396

515

720

767

944

1076

1102

1411

1732

2127

min

313

513

544

619

752

868

896

1159

1368

1710

max

16.2

40.4

19.9

27

34.3

23.8

30.3

14.2

20.2

35.9

med

16.1

37.1

17

23.4

32.7

22.7

27

12.5

19.9

32.6

min

13.2

28.9

12.3

17.7

23.1

17.5

22

9.6

13.8

21.6

max

3.09

3.77

5.7

7.47

8.69

9.45

10.9

12.9

15.6

med

2.97

3.7

4.8

5.56

7.21

8.28

9.12

10.3

12.3

14.7

7.12

min

2.3

2.9

3.74

4.58

5.66

6.64

7.39

8.3

9.6

11.3

max

447

633

785

918

1145

1274

1390

1584

1890

2412

med

428

612

756

886

1094

1210

1328

1498

1800

2232
1764

min

331

479

576

734

882

990

1101

1238

1451

max

14.3

26.8

18.2

21.3

30.8

22

28.3

13.8

19

33.8

med

14

25.6

15.7

19.7

29.6

21

25.3

12.3

17.9

30.6

min

11.3

20.2

11.3

15.6

20.4

16

20.1

9.3

12.5

19.2

max

2.23

2.91

3.69

4.6

5.64

7.18

7.93

7.79

9.32

11.8

med

2.20

2.83

3.54

4.36

5.49

6.94

7.74

7.39

9.15

11.3

min

1.91

2.44

2.99

3.63

4.58

6.02

6.74

6.2

7.35

9.38

max

191

252

316

396

486

619

684

670

809

1011

med

173

245

306

375

472

598

666

637

788

972

min

166

209

260

313

393

518

580

533

633

806

max

8.34

14.4

23.7

37.4

56.6

102

129

35.5

53.9

93.1
86.7

med

8.1

13.7

22

33.8

53.8

95.6

123

32.2

52.1

min

6.3

10.5

16.1

24.1

38.4

73.4

94.7

23.2

34.6

61

max

405

575

739

944

1099

1318

1408

1730

1979

2404

med

390

540

690

854

1040

1220

1334

1578

1913

2214

min

290

390

505

630

745

904

999

1148

1310

1555

max

54

56

59

62

64

64

62

66

66

68

med

53

54

57

59

62

63

60

63

64

66

min

45

47

50

53

56

58

53

55

54

61

139

202

214

257

Power supply [V-ph-Hz]

230 / 1/ 50 + E

Power input [W]

Dimensions

6.24

7.71

3.76

max

37

49

66

89

120

145

Height mm

560

560

560

560

560

560

560

560

560

560

Width

mm

840

940

1040

1122

1260

1460

1560

1660

1860

2160

Depth mm

263

263

263

263

263

263

263

263

263

263

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C
(2) Room temperature 20C - Water inlet temperature: 50C
(3) Room temperature 20C - Water inlet temperature: 70/60C
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

16

fan coils & terminal range 2008

YHK
Hydro Cassette
2 & 4 pipe system

A complete range from 1.3 kW to 11.1 kW

Coloured versions available as a option

Features

YHK Hydro Cassette units are simple and elegant,


discreet in their design. High standards of quality and
reliability, combined with a wide range of accessories
ensure a total solution for your comfort cooling and
heating requirements.

Cooling duty from 1.3 to 11.1 kW


2 & 4 pipes systems in all range
2 sizes: 600 x 600 & 800 x 800
Possible to choice between 6 fan speeds
Condensate pump integrated in all range
2/3 way valves fitted or supplied loose in all range
Coloured versions, posible to change the colour of
the grill and the frame
Possible to select a complete range of controls
Electric heater fitted as an option for all range
(2 pipe only)
All metal parts insulated to avoid condensations

Selection software

17

YHK Hydro Cassette


1.3 kW to 11.1 kW
Technical features
Model -2 pipes
Total cooling capacity 2 Pipes [kW]

(1)

Sensible cooling capacity 2 Pipes [kW]

(1)

Water flow in cooling 2 Pipes [l/h]

(1)

Pressure drop in cooling 2 Pipes [kPa]

(1)

Heating capacity 2 pipes [kW]

(2)

Water flow in heating 2 pipes [l/h] *

(2)

Pressure drop in heating 2 pipes [kPa]

(2)

Heating capacity 2 pipes [kW]

(3)

Water flow in heating 2 pipes [l/h]

(3)

Pressure drop in heating 2 pipes [kPa]

(3)

YHK 20-2

YHK 25-2

YHK 40-2

YHK 50-2

YHK 65-2

YHK 95-2

YHK 110-2

max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min

2.0
1.6
1.3
1.6
1.3
1.0
340
280
219
10
7
4.5
2.6
2.1
1.6
340
280
219
9
6
4
4.6
3.7
2.8
393
315
240
9.9
6.5
4
YHK 20-4

2.7
2.3
1.8
2.0
1.8
1.4
461
402
316
9.7
7.6
4.9
3.4
2.9
2.2
461
402
316
8.2
6.3
4.1
5.7
4.9
4.2
488
422
360
8.4
6.4
4.8
YHK 25-4

4.3
3.3
2.3
3.2
2.4
1.6
745
574
387
15.1
9.4
4.6
5.2
3.9
2.6
745
574
387
11.4
7.3
3.5
9.3
7
4.9
795
598
415
12.5
7.6
4
YHK 40-4

5.0
3.9
2.9
3.7
2.8
2.1
863
667
506
19.7
12.4
7.5
6.2
4.6
3.4
863
667
506
17.7
11.2
6.7
10.6
8.3
6.1
914
709
524
16
10
5.9
YHK 50-4

6.2
4.9
4.2
4.6
3.6
3.0
1 060
845
724
21.6
14.3
10.9
7.8
6.0
5.1
1060
845
724
15.1
9.9
6.7
13.1
10.7
8.6
1130
874
741
17.5
11.3
8.4
YHK 65-4

9.5
6.8
5.3
6.5
4.5
3.5
1 636
1 166
913
26.9
14.7
9.4
11.7
8.0
6.1
1636
1166
913
23
12.4
7.9
19.8
13.4
10.3
1699
1155
882
20.9
10.6
6.7
YHK 95-4

11.1
8.5
5.3
8.3
6.1
3.7
1 909
1 453
913
35.6
21.8
9.4
14.0
10.3
6.1
1909
1453
913
30.6
18.6
7.9
23.7
17.3
10.3
2037
1484
882
28.9
16
6.7
YHK 110-4

max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min
max
med
min

2.3
2.0
1.5
1.9
1.6
1.2
401
337
260
13.5
10
6
3.0
2.5
2.0
261
219
169
14.5
10.5
6.5
610
420
310
49
40
33
40
31
24

2.7
2.4
1.9
2.0
1.7
1.3
464
406
318
8.8
6.9
4.6
3.5
3.0
2.4
298
260
209
10.8
8.5
5.7
520
420
310
45
40
33
36
31
24

3.3
2.7
1.9
2.6
2.0
1.3
574
456
318
13.4
8.8
4.6
4.4
3.5
2.4
378
298
209
16.6
10.8
5.7
710
500
320
53
45
33
44
36
24

6.3
5.0
4.1
4.7
3.7
3.0
1090
865
712
18.9
12.5
8.8
9.1
7.2
5.9
783
618
508
21.4
14
9.8
1140
820
630
48
40
33
39
31
24

7.7
5.7
4.5
5.8
4.2
3.3
1326
974
777
26.9
15.4
10.3
11.0
8.1
6.5
946
697
555
29.9
17.4
11.5
1500
970
710
53
40
34
44
31
25

8.9
6.9
4.5
6.8
5.2
3.3
1529
1192
777
34.7
22.1
10.3
12.7
10.0
6.5
1092
858
555
38.8
25.3
11.5
1820
1280
710
58
48
34
49
39
25

max
max

44
0.20
8.0
275
575
575

44
0.20
1.4
275
575
575

68
0.32
2.1
275
575
575

3.8
3.0
2.4
3.0
2.3
1.8
655
519
406
17
11.2
7.2
5.0
4.0
3.1
426
341
267
20.5
13.8
8.8
880
610
430
59
49
41
50
40
32
230V/1ph/50hZ
90
0.45
2.1
275
575
575

77
0.36
3.0
303
820
820

120
0.53
4.0
303
820
820

170
0.74
4.0
303
820
820

Model -4 pipes
Total cooling capacity 4 Pipes [kW]

(1)

Sensible cooling capacity 4 Pipes [kW]

(1)

Water flow in cooling 4 pipes [l/h]

(1)

Pressure drop in cooling 4 pipes [kPa]

(1)

Heating capacity 4 pipes [kW]

(3)

Water flow in heating 4 pipes [l/h]

(3)

Pressure drop in heating 4 pipes [kPa]

(3)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)]


Power supply [V-ph-Hz]
Power input [W]
Absorbed current [W]
Water content (2 pipes) [l]
Dimensions

(4)

Height mm
Width mm
Depth mm

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C
(2) Room temperature 20C - Water inlet temperature: 50C
(3) Room temperature 20C - Water inlet temperature: 70/60C
(4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

18

fan coils & terminal range 2008

YHH
Hydro High Wall
2 & 4 pipe system

A complete range from 1.4 kW to 4.0 kW

Integrated Valve Kit

Features

YHH Hydro High Wall units are simple and elegant,


discreet in their design. High standards of quality and
reliability, combined with a wide range of accessories
ensure a total solution for your comfort cooling and
heating requirements.

Wired control or infrared control


Automatic Air Sweep
Integrated Valve kit
Condensate pump (accessory)
Stylish front cover
Master-Slave control

Selection software

19

YHH Hydro High Wall


1.4 kW to 4.0 kW
Technical features
Model
Total cooling capacity [kW]

Sensible cooling capacity [kW]

(1)

(1)

Water flow in cooling [l/h]

(1)

Pressure drop in cooling [kPa]

(1)

Heating capacity 2 pipes [kW]

(2)

Water flow in heating 2 pipes [l/h] *

(2)

Pressure drop in heating 2 pipes [kPa]

(2)

Heating capacity 2 pipes [kW]

(3)

YHH 15

YHH 30

YHH 50

max

1.4

2.3

4.0

med

1.3

3.6

min

1.1

1.8

3.2

max

1.0

1.5

2.5
2.2

med

0.9

1.3

min

0.8

1.2

1.9

max

252

420

700

max

25

10.5

24

max

1.8

2.8

5.1
4.6

med

1.6

2.5

min

1.4

2.2

4.1

max

250

420

700

max

23

10

23

max

3.1

4.7

8.4

med

2.8

4.2

7.6

min

2.5

3.7

6.7
700

Water flow in heating 2 pipes [l/h]

(3)

max

250

420

Pressure drop in heating 2 pipes [kPa]

(3)

max

25

10.5

23

max

3.0

3.5

4.4

Heating capacity 4 pipes [kW]

(3)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)]

(4)

med

2.5

3.0

3.5

min

2.0

2.4

2.4

max

360

474

648

med

240

318

450

min

150

198

264

max

38

41

48

med

37

38

45

min

35

35

42

max

35

38

45

med

34

35

42

min

32

32

39

Power supply [V-ph-Hz]

230 / 1 / 50 + E

Power input [W]

max

28

41

58

Absorbed current [A]

max

0.13

0.18

0.25

Water content (2 pipes) [l]


Dimensions

Height mm

270

320

330

Width

mm

870

1 030

1 160

Depth mm

176

196

198

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C
(2) Room temperature 20C - Water inlet temperature: 50C
(3) Room temperature 20C - Water inlet temperature: 70/60C
(4) Sound pressure level in a 100 m2 room, at 1 m distance and riverberating time of 0,3 s.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

20

fan coils & terminal range 2008

YEFB
Hydro Blower
2 & 4 pipe system

A complete range from 4 kW to 24 kW

Features
Our YEFB Blower units are available in 4 sizes for
horizontal concealed installations: thanks to their high
ESP fans that can handle up to 250Pa, they are the
ideal solution for air conditioning and heating large
environments.

Selection software

4 unit sizes for horizontal mounting


Handles high external static pressure up to 250Pa
Choice of 2 or 4 pipe systems
Air distribution plenum
Electric heater option
Optional paint finish
F5 grade filter option

21

YEFB Hydro Blower


4 kW to 24 kW
Technical features at 50 Pa external static pressure
Model
max
Total cooling capacity [kW]

Sensible cooling capacity [kW]

Water flow in cooling [l/h]

Pressure drop in cooling [kPa]

Heating capacity 2 pipes [kW]

Water flow in heating 2 pipes [l/h] *

Pressure drop in heating 2 pipes [kPa]

Heating capacity 4 pipes [kW]

Water flow in heating 4 pipes [l/h]

Pressure drop in heating 4 pipes [kPa]

(1)

(1)

(1)

(1)

(2)

(2)

(2)

(3)

(3)

(3)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)]

(4)

YEFB 130

YEFB 140

YEFB 230

YEFB 240

YEFB 330

YEFB 340

YEFB 430

YEFB 440

6.01

6.92

8.81

10.61

11.15

14.06

17.86

23.31

med

5.13

5.81

7.27

8.55

9.39

11.58

16.28

20.95

min

3.22

3.49

6.08

7.01

7.51

9.00

14.40

18.21

max

4.72

5.29

7.45

8.71

9.13

11.2

14.39

17.73

med

3.95

4.36

5.9

6.74

7.48

8.95

12.86

16.5

min

2.38

2.52

4.79

5.37

5.81

6.75

11.57

13.34

max

1033

1189

1515

1824

1916

2417

3071

4008

med

882

999

1250

1470

1615

1991

2798

3602

min

554

600

1045

1205

1291

1547

2475

3130

max

6.3

20.6

70.9

43.8

45.1

39.6

23.7

21.9

med

27.4

15.2

50.5

30

33.4

28.2

20.1

18.1

min

12.1

6.2

36.9

21.1

22.5

18.1

16.1

14

max

8.24

9.25

13.08

15.44

16.02

19.76

25.46

31.27

med

6.87

7.57

10.34

11.89

13.08

15.69

22.69

27.48

min

4.08

4.3

8.36

9.4

10.1

11.72

19.55

23.26

max

1430

1604

2269

2678

2779

3426

4414

5421

med

1192

1313

1793

2061

2268

2721

3934

4765

min

708

746

1451

1630

1752

2033

3390

4032

max

51.8

28.3

116.8

69.7

70.2

59.2

38.2

31.6

med

37.6

19.9

77.2

44

49.1

39.5

31

25.1

min

15

7.4

53.2

29.1

31.2

23.6

23.7

18.6

max

13.19

21

25.7

41.1

med

10.98

16.57

20.96

36.66

min

6.5

13.37

16.17

31.58

max

1154

1836

2247

3596

med

961

1449

1833

3205

min

568

1169

1414

2761

max

33.1

75

45

24.8

med

24

49.4

31.5

20.2

min

9.5

33.9

19.9

15.4

max

1153

1130

2158

2116

2639

2587

4129

4048

med

916

898

1553

1523

1994

1955

3505

3436

min

494

484

1174

1151

1422

1394

2853

2797
78

max

67

67

71

71

71

71

78

med

62

62

65

65

65

65

75

75

min

52

52

60

60

59

59

70

70

max

57

57

61

61

62

62

69

69

med

52

52

56

56

56

56

66

66

min

43

43

50

50

50

50

61

61

Power supply [V-ph-Hz]

230 / 1 / 50

Power input [W]

max

186

186

419

419

569

569

984

984

Absorbed current [W]

max

0.81

0.81

1.95

1.95

2.59

2.59

4.45

4.45

Height mm
Dimensions

Width

mm

Depth mm

331

331

331

331

350

350

439.3

439.3

989.6

989.6

989.6

989.6

1 239.6

1 239.6

1 633

1 633

800

800

800

800

900

900

900

900

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C
(2) Room temperature 20C - Water inlet temperature: 50C
(3) Room temperature 20C - Water inlet temperature: 70/60C
(4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397
4 pipe system not available with 4R coil

Manufacturer reserves the rights to change specifications without prior notice.

22

fan coils & terminal range 2008

ECOFRIO v2
Air Cooled Chiller / Heat Pump
From 5 kW up to 40 kW - R410A

YLAE TEMPO
Air Cooled Scroll Compressor Chiller
Cooling Capacities: 172-465 kW - R410A

ECOFRIO
Air Cooled Chiller / Heat Pump
From 50 kW up to 156 kW - R410A / R407C

YLAE-HP TEMPO
Reverse Cycle Air to Water Heat Pump Chiller
Heating Capacities: 187-469 kW - R410A
Cooling Capacities: 183-426 kW - R410A

HVS (Hydro Variable System)


Air Cooled Chiller / Heat Pump
Compact and Split Version
From 15 kW up to 72 kW - R407C

YCIV SYMPHONY
Air-Cooled Variable Speed Drive
Screw Compressor Chiller
Cooling Capacities: 540-1405 kW - R134A

YLCC
Air Cooled Chiller / Heat Pump
Centrifugal fan, indoor installations
From 40 kW up to 137 kW - R407C

YCSE
Water-Cooled or Remote Air-Cooled
Screw Compressor Chiller
Cooling Capacities: 134-320 kW - R407C

23

YCWL ZAFIRO
Water-Cooled or Remote Air-Cooled
Scroll Compressor Chiller
Cooling Capacities: 188-580 kW - R410A

YNWS/RS
Water-Cooled or Remote Air-Cooled
Screw Compressor Chiller
Cooling Capacities: 470-1790 kW - R717
Coefficient of Performance as high as 5.5

YLCS
Water-Cooled or Remote Air-Cooled
Screw Compressor Chiller
Cooling Capacities: 336-1090 kW - R134A

YNWH
Water-Cooled Screw Chiller
Brine Applications
Cooling Capacities: 300-1200 kW - R507

YN
Water-Cooled Screw Chiller
Dry Cooler Application
Heat Recovery Application
Cooling Capacities: 570-1300 kW - R134A
Coefficient of Performance as high as 6.0

YK
Water-Cooled Centrifugal Compressor
Chiller
Cooling Capacities: 800-8500 kW - R134A
Coefficient of Performance as high as 7.0

YR
Water-Cooled Screw Compressor Chiller
Cooling Capacities: 700-1350 kW - R134A
Coefficient of Performance as high as 6.0

YMA
Custom Air Handling Units
Air Volume Range 0.25 m3/s to 60 m3/s

Manufacturer reserves the rights to change specifications without prior notice.

2008 Johnson Controls, Inc.

www.johnsoncontrols.com
Printed on recycled paper