Hvac Calculation

1) The document provides information for comparing the ventilation requirements of a room in Mumbai with an area of 269.19 sqft and a height of 10.76 ft. 2) Key details include an occupancy of 5 people, equipment load of 0 kW, fresh air changes per hour of 1, and room air changes per hour of 1. 3) Calculations are shown for the sensible and latent heat loads on the room from various sources like walls, glass, lights, people, and infiltration. The total sensible and latent heat loads are calculated.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
200 views

Hvac Calculation

1) The document provides information for comparing the ventilation requirements of a room in Mumbai with an area of 269.19 sqft and a height of 10.76 ft. 2) Key details include an occupancy of 5 people, equipment load of 0 kW, fresh air changes per hour of 1, and room air changes per hour of 1. 3) Calculations are shown for the sensible and latent heat loads on the room from various sources like walls, glass, lights, people, and infiltration. The total sensible and latent heat loads are calculated.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Job : Comparison

Location : Mumbai
Space : Zone 2 BY ANUBHAVSAXENA
Unit in Ft. : W Length Area F/C Height Volume 16 Hours
Size : 0 0 269.19 10.76 2896 4.00pm Date :
Clean Room Class : NIL Out Side DB deg.F WB deg.F Drange %RH DP GR/LB
Filtration : 10 Micron Summer 96 83 32 60 0 92
Pressure Gradient : NIL Monsoon 85 82 88 162
Lighting Load : 0.9 Watts / Sq.ft. Room 71.58 61 55 0 64
Occupancy : 5 Nos. T : 24.42 32 Gr/Lb : 28
Equipment Load : 0.0 KW VENTILATION:
CFM / Person : 15 5 People 15 CFM/Per 75
Correction Factor : 12 269.19 Sq.ft. 10.76 HT. x 1 48
Coil By Pass Factor. : 0.1 Row Deep Coil. 4 Select : 75
Fresh Air Changes/Hr.: 1 Effective Room Sensible Heat Factor ( ERSHF ) :
Weight OF Wall: 60
Heatload for(summmer/monsoon) summer
Room Air Changes/Hr.: 1 48 CFM 9284 Effective Room Sensible Heat
= 0.90
Glasses Area In Sun Gain / Temp. 'U'Factor Heat 10355 Effective Room Total Heat
Sq.ft. In Deg. F Btu / Hr. Apparatus Dew Point. :( A.D.P.) Indicated = 54
Glass W 0.00 163 0.30 0 Selected = 61
Glass E 0.00 12 0.30 0 Dehumidified Rise =
Glass N 26.90 23 0.70 433 (1-B.F.) x (RM.TEMP- A.D.P.)
Glass S 26.90 12 0.70 226 0.90 x 10.58 = 9.522
Glass NW 0.00 138 0.30 0
Glass SW 0.00 85 0.30 0 Dehumidified CFM = 9284 (E.R.S.H.)
Glass NE 0.00 12 0.30 0 1.08 x 9.52 (Deh. Rise)
Glass SE 0.00 12 0.30 0

Walls Eq.Temp. Dehum. CFM = 903


Diff. : Supply Air CFM = 903
Wall W 176.44 37 0.28 1834
Wall E 0.00 30 0.28 0 Coil By Pass CFM = 0
Wall N 182.00 22 0.28 1121 CFM / Sq.ft. = 3.4
Wall S 182.00 35 0.28 1784 Sq.ft. / TR = 234
Wall NW 0.00 24 0.16 0 ROOM LATENT GAIN :
Wall SW 0.00 44 0.16 0 Infiltration 28 gr/lb 0.68 200
Wall NE 0.00 24 0.16 0 People 5 NO. X 175 Gain/Person 700
Wall SE 0.00 30 0.16 0 Steam Lb/Hr. X 1080 0
Roof SUN 269.19 40 0.09 0 Vap.Trans. 0 0.01 28 gr/lb 0
Roof SHA 0.00 20 0.40 0 Permeation Load
All Glass 53.80 29 0.47 744 ROOM LATENT HEAT SUBTOTAL: 900
Partition 0.00 19 0.30 0 Supply Duct Leackage Loss & Safty Factor : 5% 45
PartitionGl. 0.00 19.42 0.30 0 Out.Air 75 28 0.1 B.F. 0.68 126
Ceiling 0.00 19.42 0.02 0 EFFECTIVE ROOM LATENT HEAT : 1071
Floor 0.00 19.42 0.38 0 EFFECTIVE ROOM TOTAL HEAT : 10355
People 5 No. X 270 Gain/Person. 1350 Out Side Air Heat : T x (1 - B.F.) x Factor = BTU / Hr.
Eqp Load 0.00 No. X 3410 Gain/KW 0 Sensible 75 24.42 T 0.90 1.08 1780
Lights 247.65 Watts X 1 X 3.40 842 Latent 75 28 gr/lb 0.90 0.68 1285
Appliance 0.00 Watts X 3.40 0 GRAND TOTAL HEAT SUBTOTAL : 13420
Product Load Safety Factor : 0.03 403
ROOM SENSIBLE HEAT SUBTOTAL : 8334 Roof Sun 32 0 0
Supply Duct Heat Gain : 2% 0 0 0
Safety Factor : 5% Roof SHA 8 0 0
Fan Heat Gain : 5% 417 Ceiling 19.42 0 0
Out.Air 75 24.42 0.10 B.F. 1.08 198 GRAND TOTAL HEAT : 13823
Infiltration 335
EFFECTIVE ROOM SENSIBLE HEAT : 9284 LOAD TR : 1.2
ROOM SENSIBLE HEAT FACTOR : 0.90
GRAND ROOM SENSIBLE HEAT FACTOR : 0.67