Hvac Calculation
Hvac Calculation
Location : Mumbai
Space : Zone 2 BY ANUBHAVSAXENA
Unit in Ft. : W Length Area F/C Height Volume 16 Hours
Size : 0 0 269.19 10.76 2896 4.00pm Date :
Clean Room Class : NIL Out Side DB deg.F WB deg.F Drange %RH DP GR/LB
Filtration : 10 Micron Summer 96 83 32 60 0 92
Pressure Gradient : NIL Monsoon 85 82 88 162
Lighting Load : 0.9 Watts / Sq.ft. Room 71.58 61 55 0 64
Occupancy : 5 Nos. T : 24.42 32 Gr/Lb : 28
Equipment Load : 0.0 KW VENTILATION:
CFM / Person : 15 5 People 15 CFM/Per 75
Correction Factor : 12 269.19 Sq.ft. 10.76 HT. x 1 48
Coil By Pass Factor. : 0.1 Row Deep Coil. 4 Select : 75
Fresh Air Changes/Hr.: 1 Effective Room Sensible Heat Factor ( ERSHF ) :
Weight OF Wall: 60
Heatload for(summmer/monsoon) summer
Room Air Changes/Hr.: 1 48 CFM 9284 Effective Room Sensible Heat
= 0.90
Glasses Area In Sun Gain / Temp. 'U'Factor Heat 10355 Effective Room Total Heat
Sq.ft. In Deg. F Btu / Hr. Apparatus Dew Point. :( A.D.P.) Indicated = 54
Glass W 0.00 163 0.30 0 Selected = 61
Glass E 0.00 12 0.30 0 Dehumidified Rise =
Glass N 26.90 23 0.70 433 (1-B.F.) x (RM.TEMP- A.D.P.)
Glass S 26.90 12 0.70 226 0.90 x 10.58 = 9.522
Glass NW 0.00 138 0.30 0
Glass SW 0.00 85 0.30 0 Dehumidified CFM = 9284 (E.R.S.H.)
Glass NE 0.00 12 0.30 0 1.08 x 9.52 (Deh. Rise)
Glass SE 0.00 12 0.30 0