The Alerton® VisualLogic® VLC-550-E is a versatile, BACnetcompliant, fully programmable field controller designed for fan coils, a/c-units, heat pumps, and other terminal unit applications. As a native BACnet controller, it integrates seamlessly with your BACnet system, communicating at up to 115 Kbps on a BACnet MS/TP LAN

Uploaded by

ngmuthu1981
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
479 views

VLC-550 Data Sheet

The Alerton® VisualLogic® VLC-550-E is a versatile, BACnetcompliant, fully programmable field controller designed for fan coils, a/c-units, heat pumps, and other terminal unit applications. As a native BACnet controller, it integrates seamlessly with your BACnet system, communicating at up to 115 Kbps on a BACnet MS/TP LAN

Uploaded by

ngmuthu1981
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

VLC-550-E

The Alerton® VisualLogic® VLC-550-E is a versatile, BACnet-


compliant, fully programmable field controller designed for fan
coils, a/c-units, heat pumps, and other terminal unit applications.
As a native BACnet controller, it integrates seamlessly with your
BACnet system, communicating at up to 115 Kbps on a BACnet
MS/TP LAN.
The VLC-550-E supports the Alerton Microtouch™, as
well as the BACtalk® Microset, Microset II, and Microset 4
intelligent wall sensors, which offer convenient data display,
setpoint adjustment, and technician access to equipment setup
parameters.
All VLC-550-E control logic is programmed using Alerton's
easy-to-learn graphical programming language, VisualLogic™.
Programming and setup data are stored in non-volatile flash
memory, ensuring stable and reliable operation.
High-resolution 16-bit universal inputs are auto-selectable for
thermistor, dry contact, pulse, 0-5 V, 0-10 V, or 4-20 mA.
VISUALLOGIC® UNITARY
FIELD CONTROLLER
FEATURES AND HIGHLIGHTS
• Fully BACnet-compliant on MS/TP LAN at up to 115.2 Kbps.
• Programmable control logic can be field-modified.
• Downloadable operating code to allow for future
software improvements
• 32-bit processor architecture with all program data backed up
in nonvolatile flash memory.
• High-speed processing of DDC program, with an internal
logical loop time of 100 msec.
• Backwards compatible with older VLC-550 and VLC-550C3
models.

APPLICATIONS
Recommended for unit ventilator and fan-coil applications, or any
application that requires multi-speed fan or motor control.

VLC-550-E

UI HBO GBO RO AO AF F
UNIVERSAL HOT SWITCHED TRIAC GROUND SWITCHED
INPUTS BINARY OUTPUTS BINARY OUTPUTS RELAY OUTPUT ANALOG OUTPUTS AIR-FLOW SENSOR FILTER

5 5 0 0 0 - -
© 2019 Honeywell International Inc. All Rights Reserved. LTDATA-VLC-550-E 1219 1
VLC-550-E

TECHNICAL DATA ORDERING INFORMATION


POWER – 24 VAC @ 50-60 Hz. 9 VA minimum (maximum 90 ITEM NUMBER
VA with loads). Half-wave rectified. VLC-550-E ALERTON VISUALLOGIC
INPUTS – 16-bit universal inputs accept 3k (Ibex) or 10k CONTROLLER BACNET
thermistor (type II), dry contact, 0-20 mA, 0-10 V, 0-5V, or
dry-contact pulse. External 250-ohm resistor required for 0-20 CERTIFICATION AND CONFORMANCE
mA inputs. Pulse input maximum frequency of 100 Hz. Pulse BACNET CONFORMANCE – An application specific
input minimum duty cycle 5mS ON / 5mS OFF (pulse input not controller (ASC) level device; tested and approved by BTL. See
supported on IN-0). Protocol Implementation Conformance Statement (PICS).

POWER OUTPUT FOR EXTERNAL SENSORS – 20 UL – Listed Underwriters Laboratory for Open Energy
VDC ±10% @ 100 mA maximum Management Equipment (PAZX) under the UL Standard for
Safety 916; listing includes both U.S. and Canadian certification.
BINARY OUTPUTS – Triacs rated 24 VAC @ 50/60 Hz, 500
mA continuous and 800 mA (AC rms) for 60 milliseconds. EMC – EMC Directive 89/336/EEC (European CE Mark).

MICROSET – Supports BACtalk® Microset, Microset II, or FCC – This device complies with part 15 of the FCC Rules.
Microset 4 on input 0 (IN-0). Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device
INPUT/OUTPUT TERMINATIONS – Removable header- must accept any interference received, including interference that
type screw terminals accept 14-24 AWG wire. may cause undesired operation.
MAX DIMENSIONS – 4.9" (125mm) H x 5" (127mm) W x
1.4" (36mm) D
MOUNTING – Screw mounting
ENVIRONMENTAL – 0 to 158°F (-17 to 70°C) / 5 to
95%RH, non-condensing
COMMUNICATIONS – EIA-485 (RS-485) over twisted
shielded-pair (TSP); auto-baud switching (9.6kbps, 19.2kbps,
38.4kbps, 76.8kbps, or 115.2kbps); communication status LED.
PROTOCOLS – BACnet MS/TP (master)
PROGRAMMING – Supports Alerton’s BD4 DDC file format
using Alerton’s VisualLogic® toolset.
MICROPROCESSOR – 32-bit ARM Cortex-M4F, 80 MHz
MEMORY – 512 MB non-volatile flash.
SECURITY – Integrated secure boot prevents loading of
tampered firmware.