PROJECT TITLE:
SAUDI ARAMCO DAMMAM STADIUM
100% DETAILED DESIGN AND IFC FOR
FIT-OUT: ARCHITECTURAL
COMPLIANCE STATEMENT
SPECS / DRAWING IDENTIFYING ANY DEVIATION
PROPOSED PRODUCT / PRODUCT COMPLIANCE TO THE
REF. I.E. SPECIFICATION REQUIREMENT FROM SPECIFICATION &
PROPERTIES SPECIFICATION
SECTION, PAGE NO JUSTIFICATION
SECTION 07 84 00 PART 1 - GENERAL BOSTIK FP310 Intum escent Acoustic The resistance to fire performance
Acrylic COMPLY test standards most commonly
FIRE STOPPING 1.2.1 Perform ance Requirem ents:
Provide Fire stop materials and systems produced, Fire-retardant Intumescent Acrylic Sealant referred to are the British Standards
tested and installed to resist the spread of fire and the (BS 476: Parts 20 to 24). The
passage of smoke and gases through openings in fire Bostik FP310 Intumescent Acoustic Acrylic is European Norms (EN 1363 to 1366)
rated assemblies. Design and install the Firestopping a fire rated single component acrylic sealant w ill gradually replace BS 476.
system(s) so that penetrating items may be removed or specially designed for fire sealing. Bostik FP (https://w w w .uktestcert.com/post/bs
inserted after installation of the Firestopping system(s) 310 Intumescent Acoustic Acrylic expands 476-en-standards)
w hile still maintaining the required fire resistance of the w hen heated and produces an efficient seal
system. against fire, smoke and gas.
1.2.4 Through Penetration Fire stop System s:
Provide systems tested in accordance w ith BS476 Technical Properties:
methods for type of penetration required. Provide a seal *Reaction to Fire: Class D-s1, d1
completely filling all annular spaces to prevent the *Expansion Rate: 1:2-3
passage of flame, smoke and toxic gases through the *Movement Capabilities: ±12.5%
opening in the fire rated construction in w hich it is *Durability: Z2
installed. When the penetrating items are subject to *Sound Insulation: 62 dB
movement, the Firestop systems shall be based upon
elastomeric Firestop sealant such that movement of the Certifications:
penetrations shall not affect the adhesion or integrity of * EN 1366-4 (EN equivalent to ASTM E-1966)
the Fire stop system. * EN 1366-3 (EN equivalent to ASTM E814)
1.2.7 Surface Burning Characteristics: * UL tested and certified (Ref: UL-EU-01134-
Provide Firestop materials rated as required by law s, CPR)
codes, ordinances and regulations, w hen tested in * UL-UK EC Certificate of Constancy of
accordance w ith BS476, Part 7, for flame spread and Performance, ref: 0843–CPR–0517
BS6401, for smoke development. * EOTA tested and certified (Ref: ETA-
1.2.9 Building Movem ent: 19/0396 & ETA-19/0397)
Provide Fire stop systems suitable to w ithstand building * European Assessment Document
movements, including thermal movements, loading (hereinafter referred to as EAD): EAD
deflection, shrinkage, creep and similar movements. 350454-00-1104 (passage seals) and EAD
Such Firestop systems w ill not compromise the smoke 350141-00-1106 (sealing of linear
and fire seal w hilst allow ing for such movements. connections)
1.2.11 Material Content: * A+ French VOC Regulation
Provide Fire stop materials w hich are non-toxic, non * M1 Finnish VOC Certification
hazardous, and do not containasbestos fibers or dust
particles or other substance prohibited by law . LEED:
PART 2 PRODUCTS *VOC Content (SCAQMD Rule 1168): Pass
2.1 MATERIALS *VOC Emission (CDPH / Emicode): Pass
Provide the miscellaneous accessory items necessary *LEED Attestation: Yes
to complete each Firestopping condition, including, but
not limited to, fillers, mechanical fastenings, support
devices, collars, sleeves, and other materials, as made
or recommended by the Firestop material manufacturer
and tested w ith the rated Fire stop system.
Fire stops Sealant:
For use in small openings of 300 mm diameter or less,
penetrations subject to movement, in noncombustible
pipes, noncombustible conduits, noncombustible ducts,
control joints, slab edge and exterior w all voids, as a
sealant for smoke barrier construction, fire and smoke
dampers, head of w all details and fire doors in masonry
or gypsum dryw all partitions.
2.1.2 Intum escent Sealant:
Graphite based, one part Intumescent paste unaffected
by w ater or moisture w hen cured containing no
solvents, inorganic fibers, or silicone compounds.
2.1.3 Intum escent Graphite Based Sealants:
One part graphite based Intumescent sealant
unaffected by w ater or moisture w hen cured.
END OF SECTION 07 84 00