Three Phase Transformers
Three Phase Transformers
TRANSFORMEs
TRANSFORMER
TRANSFORMER
In modern power system, almost the entire electricity al energy
is generated, transmitted and distributed by using three phase
system.
During this voltage is raised or lowered several times for
economic reason.
When three identical units of single phase transformer are used
then the arrangement is called as Bank of Three Transformers
or Three-Phase Transformer Bank.
A B C
a b c
TRANSFORMER
In modern power system, almost the entire electricity energy
is generated, transmitted and distributed by using three phase
system.
During this voltage is raised or lowered several times for
economic reason.
When three identical units of single phase transformer are used
then the arrangement is called as Bank of Three Transformers
or Three-Phase Transformer Bank.
A B C
a b c
TRANSFORMER
Evolution of Three Phase Transformer:
II
1200
1200
I
III
The primary and secondary windings are wound over the limbs I,
II and III.
All the three primary windings are excited.
TRANSFORMER
Evolution of Three Phase Transformer:
The flux of one phase, completes its path through other two limbs.
TRANSFORMER
Evolution of Three Phase Transformer:
TRANSFORMER
Evolution of Three Phase Transformer:
For the flux all phases A, B & C, there is equal air gap, equal
reluctance and equal magnetizing current.
Iμa= Iμb= Iμb
TRANSFORMER
Evolution of Three Phase Transformer:
II B
P
A I S
P C
S
P
S
III
A I II III
B C
P P P
S S S
A I II III
B C
P P P
S S S
Shell Type
TRANSFORMER
Three Phase Shell type Transformer:
Winding is surrounded by core.
By placing three
1 2 3 4 single phase shell
type transformers side
by side, three phase
shell type transformer
A B C is formed.
If winding A is excited,
flux is set up
TRANSFORMER
Three Phase Shell type Transformer:
Winding is surrounded by core.
By placing three
1 2 3 4 single phase shell
type transformers side
by side, three phase
shell type transformer
A B C is formed.
If winding A is excited,
flux is set up
ΦA
A B C ΦA/2
ΦB
A B
2
2 2
With ΦA is the reference phasor,
1 1
2 [0 ( 120)] [ {cos( 120) j sin( 120)}]
2 2
TRANSFORMER
Three Phase Shell type Transformer:
With ΦA is the reference phasor,
1 1
2 [0 ( 120)] [ {cos( 120) j sin( 120)}]
2 2
1 1 3 3 3
[ {( ) j ( )}] [ j ]
2 2 2 2 2 2
The magnitude is
2
3
2
3 3
2
2 2
2 2
This shows that, for same flux density, cross
3 sectional areas at 2 and 3 are 86.6% of the
central core area (Flux = B x A).
The cross sectional areas at 1 and 4 are 50% of the central
core area.
The cross sectional areas at 2 & 3 are 1.732 times areas at 1 & 4.
TRANSFORMER
Three Phase Shell type Transformer:
Now if the winding B is wound in the reversed direction.
The resultant flux Φ2 is
the phasor SUM of
1 2 3 4 ΦA/2 and ΦB/2
ΦC
ΦA/2
A B C
ΦA
ΦB/2
Φ2
ΦB
TRANSFORMER
Three Phase Shell type Transformer:
Now if the winding is wound in the reversed direction.
With ΦA is the reference phasor,
1 1
2 [0 (120)] [ {cos( 120) j sin( 120)}]
2 2
1 1 3 1 3
[ {( ) j ( )}] [ j ]
2 2 2 2 2 2
2
1
2
3
magnitudeof2 3
2 2
2 2
This shows that, for same flux density, cross sectional areas at 1, 2, 3 and
4 are SAME and equal to the one-half of the central core area.
Thus economy is effected in the core material.
Magnetic circuits are in parallel, independent of each other, similar
to Bank of Three Transformers.
TRANSFORMER
Three Phase Transformer Connections:
Winding connections are:
Star, Delta and Zig-zag (Interconnected Star or Inter Star)
Symbols are: Y, D and Z
N A B C
h. v. terminals
TRANSFORMER
Three Phase Transformer Connections:
1. Terminals are brought in rows.
2. HV and LV terminals are mounted on opposite side of tank.
3. The hv terminals have capital letters A, B, C and lv terminals
have lower case letters a, b, c.
4. Tertiary wdg, if provided, have terminals as 3A, 3B and 3C.
5. Terminals are lettered from left to right.
6. The neutral is placed on extreme left.
7. For representing connection, hv wdg is indicated by capital Y
for star, D for delta and lv wdg is indicated by lower case y for star,
d for delta.
OUTPUT
A1 N a1 n
C1 c1
INPUT
C2 b2
B1 b1
C2 c2
B2 b2 c2
B2
TRANSFORMER
Three Phase Transformer Connections:
Phasor groups:
1. Group No.1 (Zero degree phase displacement):
Yy0Connection diagram
A2 A2 A1 a1 a2 a2
OUTPUT
B2 B2 B1 b1 b2 b2
INPUT
C2 C2 C1 c1 c2 c2
N n
Dd0 A2, B2, C2 are clockwise in sequence
B1
A2 C1 A2 c1 a2
B2
or
A1 C1 C2 A1 c2 a1
C2 B1 B2 b1 b2
C2 B2 c2 b2
Line emf phasors VC2B2 and Vc2b2 are in parallel and in
one direction, in Dd0, so zero degree phase displacement
Dd0
B1
A2 C1 A2 c1 a2
B2
or
A1 C1 C2 A1 c2 a1
C2 B1 B2 b1 b2
C2 B2 c2 b2
A2 A2 a2 a2
C1 c1
C2 A1 a1 c2
C2 c2
B2 B1 B2 b1 b2 b2
Dd0
B1
A2 C1 A2 c1 a2
B2
or
A1 C1 C2 A1 c2 a1
C2 B1 B2 b1 b2
C2 B2 c2 b2
A2 A2 a2 a2
C1 c1
C2 A1 a1 c2
C2 c2
B2 B1 B2 b1 b2 b2
A2 A2 A1 a1 a2 a2
B2 B2 B1 b1 b2 b2
C2 C2 C1 c1 c2 c2
TRANSFORMER
Dz0
Lv winding is sectionalized. a2, b2, c2 are connected
a4 to form a neutral in z.
a4
a3
C1 A2 a2 a3
c1
a1 c2 a2
C2 A1 c1 b1 b2 b3 b4 c3
b1 b2
c2 c4 a1
B1 B2 c3 b3 b4
c4
C2 B2 c4 b4
Line emf phasors VC2B2 and Vc4b4 are in parallel and in same
direction, in Dz0, so zero degree phase displacement. Used in
TRANSFORMER
1. Group No.2 (1800 phase displacement):
The phase displacement between the HV and LV line emfs is
1800. The possible connections are Yy6, and Dd6.
HV
11 12 1
Y 2
10
9 1800 3
0 60 120 180 240 300 360
y 4
8
7 5
6 lv
Yy6 A2 Secondary polarities are reversed.
c1
b1
C1 A1 c2
b2 a2
B1
C2
B2
a1
Line emf phasors VC2B2 and Vc1b1 are in parallel in Yy6, but
opposite in direction, so 1800 degree phase displacement.
Yy6 A2 Secondary polarities are reversed.
c1
b1
C1 A1 c2
b2 a2
B1
C2
A2 B2
A2 a1
c1 c1
OUTPUT
b1 c2
A1 N n
C1
INPUT
C2 b2 a2
B1
C2
B2 a1
B2
a1
Yy6 A2 Secondary polarities are reversed.
c1
b1
C1 A1 c2
b2 a2
B1
C2
B2 b1
A2 A2 a1
c1 c1
OUTPUT
b1 c2
A1 N n
C1
INPUT
C2 b2 a2
B1
C2
B2 a1
B2
a1
A2 A1 a2 a1
A2 a1
B2 B1 b2 b1
B2 b1
C2 C1 c2 c1
C2 c1
N n
b1 c1
C1 A2 b1 b2
Dd6
c1
C2 A1
B1 B2 c2
C2 B2
C1 A2 b1 b2
c1
Dd6
C2 A1
B1 B2 c2
b1
C2 B2
A2 A2
C1 b1 b2 c1
c1
a2
C2 A1
C2 a1
B2 B1 B2 a1 c2
b1 c1
C1 A2 b1 b2
c1
Dd6
C2 A1
B1 B2 c2
b1
C2 B2
A2 A2
C1 b1 b2 c1
c1
a2
C2 A1
C2 a1
B2 B1 B2 a1 c2
A2 A2 A1 a2 a1 a1
B2 B2 B1 b2 b1 b1
C2 C2 C1 c2 c1 c1
TRANSFORMER
1. Group No.3 (Minus 300 phase displacement):
The phase displacement between the HV and LV line emfs is
-300. The lv line phasor lags the hv phasor by 300.
The possible connections are Yd1, and Dy1.
HV
11 12 1
300 2
Y lv
10
d 3
9
0 60 120 180 240 300 360
4
8
7 5
6
Yd1 A2
c1
c2
A1 a2
C1 c2
12 o’clock
B1 300
C2 b1 a1
B2 B2 b2
C2
Line emf phasors VB2C2 and Vb2c2 of Yd1, are having -300 degree
phase displacement.