Building Services & Integration-1: Kohinoor
Building Services & Integration-1: Kohinoor
HOPSITAL
LARGE FENESTATION
STRATEGY
KOHINOOR
CHILLER UNIT WOODGROVE
HOSPITAL 3
BANK
GREEN FEATURES
KOHINOOR HOSPITAL •(2NOS) WATER COOLED SCREW CHILLERS(COP OF
Energy Consumption (x1000kWh) 6.1)
END USE Energy Savings % •(3NOS)
Baseline Building Proposed Building FIBRE REINFORCED PLASTIC (FRP)
COOLING TOWERS EFFICIENT VARIABLE
Space cooling 1,226.6 729.10 40.56% VOLUME PUMPING SYSTEM- LOW WATER LOSS
•AHUs WITH AIRFOIL FANS AND VARIABLE
Heat Rejection 33.6 16.90 49.63%
FREQUENCY DRIVE SUITE ROOM
Space Heat 0 0 0.00% •DEMAND CONTROLLED VENTILATION(VAVs)
Hot Water 554.1 - 100% WITH CO2 SENSORS IN RECEPTION, WAITING
AREAS AND CONFERENCE ROOMS IN AIR PATH.
Ventilation Fans 805.5 197.10 75.53%
•HEAT RECOVERY SYSTEM FOR AREAS WITH
Pumps & Aux. 209.7 166.10 20.80% LARGE FRESH AIR REQUIREMENTS
•PRESSURED - INDEPENDENT VAV SYSTEMS
• USE OF R-134A REFRIGERANT IS FREE OF HCFC &
CO2
SENSORS HALONS MATERNITY
• VFD DRIVEN DOUBLE SKIN AHUs WITH LINEAR DIIFUSER
THERMAL BREAK
ACHIEVED OVERALL HVAC LOAD : 400T (1TR / 500
ACTUAL Benefit Savings:
SQFTT)
35 % Energy Savings
Better Indoor Air Quality
Regular CO2 monitoring
Increased fresh air ventilation
No sick building syndrome
Heat Reclaim System with VAV
Higher efficiency than conventional systems NICU
Healing benefits for patients
Patient Recovery Faster KOHINOOR
Based on research
WOODGROVE
HOSPITAL 4
BANK
INDOOR ENVIRONMENT QUALITY PARAMETERS
KOHINOOR HOSPITAL NO SMOKING PREMISES
MERV 13 FILTERS & CO2 SENSORS
RESULTING TO 30% INCREASE IN FRESH AIR
Green DELIVERY
Garden CONCRETE PAVERS OF SRI 35 FOR SITE DEVELOPMENT
TEMPERATURE FOR SPACES DESIGNED AT 23 deg. C +/- 1 deg C
ROOF GARDEN
• TEMPERATURE
VARIABLE FREQUENCY DRIVE (VFD)
SENSORS IN RETURN DRIVEN
& SUPPLY CHILLERS
AIR DUCT
Staircase
• MULTIPLE PRIMARY CHILLED WATER PUMPS
• SECONDARY CHILLED WATER PUMPS WITH VARIABLE
Skylight FREQUENCY DRIVES.
• CONDENSING WATER PUMPS LEED SCORE CARD
Outdoor Particulars Achieved Max. points
AHU
75% PARKING AREA SHADED BY TREES
Indoor Environmental Quality 12 15
Cooling GRASS PAVERS WHITE CHINA
MOSAIC ON TERRACE
tower Points Particulars 80.33% OF HIGH SRI ROOF AREA ACHIEVED
Credit 2.0 Water Efficiency in Air conditioning System: Reduce
Pressurisation 1 by 50%
SQUARE DIIFUSER
Unit
Solar FENESTATION
Plant DOUBLE GLAZED UNIT
ENERGY ANALYSIS & SIMULATION CAPACITY TO RETAIN &
• ORIENTATION & SHADING DEVICES REFLECT HEAT
• EVALUATE OPTIMISED ENERGY PERFORMANCE DOUBLE GLAZED UNITS WITH U VALUE 1.2
• REDUCE THE LOAD ON MECHANICAL DEVICES FOR HVAC VALUE PATIENT SUITE
SC (ALL) : 0.62
INTEGRATED ENVIRONMENTALLY BENIGN BUILDING VLT : 75% KOHINOOR
5
VLT : 75%
SHADING DEVICE: INSTALLED WOODGROVE
HOSPITAL
GROSS WINDOW TO WALL RATIO IS APPROX 27% BANK